Place of Origin: | CHINA |
Brand Name: | Tianan Electric |
Certification: | XIHARI |
Model Number: | LW39-126 |
Minimum Order Quantity: | 10 sets |
---|---|
Price: | Pending |
Packaging Details: | Standard export package |
Delivery Time: | 45 days |
Payment Terms: | L/C, T/T |
Supply Ability: | 1000 units / year |
Rated Voltage: | 110/126kV | Rated Current: | 3150A 40kA |
---|---|---|---|
Frequency: | 50/60Hz | Insulation Gas: | SF6 |
Structure: | MCCB | Standard: | IEC 60076 |
Installation: | Open Frame | Product Name: | Sf6 Vacuum Type 110kv 3150a High Voltage Vacuum Circuit Breaker 50hz |
High Light: | 110kV High Voltage Vacuum Circuit Breaker,3150A High Voltage Vacuum Circuit Breaker,SF6 vacuum type circuit breaker 50Hz |
SF6 Vacuum Type 110kV 3150A High Voltage Vacuum Circuit Breaker 50Hz
Features of SF6 Vacuum Type 110kV 3150A High Voltage Vacuum Circuit Breaker 50Hz
A. High performance of breaking, which has the capability to cut off the short-circuit and pull out of the outgoing point, and resolve the close-in fault.
B. The arc-chutes manufactured by the technology of spinning with high quality of airflow and simple structure.
C. Longer electrical service life, the ability of breaking for 20times on full capacity, and long interval for maintaining, free maintenance for 10 years under the normal operation.
D. Operation mechanism in low energy which is simple, reliable and neat.
E. Low rated pressure, not be liquefied under low temperature.
F. Smaller area occupied.
G. Low noise, used in residential areas.
H. Instant on-site installation.
Serial No. | Name | Unit | Value |
1 | Ambient temperature | ºC | -50ºC-40ºC |
2 | Rated voltage | KV | 126 |
3 | Rated power frequency withstand voltage (1min) | ||
3.1 | To earth | kV | 230 |
3.2 | Across open contact | kV | 230+73 |
4 | Rated lightning impulse withstand voltage | ||
4.1 | To earth | kV | 550 |
4.2 | Across open contact | kV | 550+103 |
5 | Rated frequency | Hz | 50 |
6 | Rated value | A | 3150 |
7 | First pole to clear factor | 1.5 | |
8 | Rated short-circuit breakering current (Isc) | kA | 40 |
9 | Rated short-circuit making current (peak) | kA | 100/104 |
10 | Rated hsort-time withstand current | kA | 40 |
11 | Rated peak withstand current | kA | 100/104 |
12 | Rated duration of short-circuit | s | 4 |
13 | Rated out of phase breaking current | kA | 10 |
14 | Short-line fault breaking current | kA | 90%Isc,75Isc |
15 | Rated line charging breaking current | A | 31.5 |
16 | Rated operating sequence | o-0.3s-CO-180s-CO | |
17 | Resistance of main contact | μΩ | ≤35 |
18 | Rated SF6 gas pressure (20ºC gauge pressure) | Mpa | 0.6 (or SF6+CF4) 50Hz |
19 | Alarm/ minimum functional pressure (20ºC gauge pressure) | Mpa | 0.55/0.50 50Hz |
20 | Annual leakage of SF6 gas | % | ≤0.5 |
21 | Gas humidity content (L/L) (20ºC at handover) | L/L | ≤150x10-6 |
22 | Mechanical endurance | Times | 10000 |
23 | Radio interference level | mv | ≤500 |
24 | Creepage distance | mm | 3906 |
25 | Weight of SF6 gas filled for each CB | kg | 8 |
26 | Weight of one set of CB | kg | 1700 |
Major Technical parameters of mechanism
No. | Name | Unit | Data | ||
1 | Energy-store motor | Normal voltage rang | V | 85%--- 110% | |
Rated voltage | DC220/AC220 | ||||
Rated power | W | 720 | |||
2 | Storage time (at rated voltage) | s | ≤20 | ||
3 | Rated voltage/current of opening coil | V/A | DC110V/4A, DC220V/2A | ||
AC220V/5A | |||||
4 | Auxiliary Switch |
Rated current | A | 3(DC220V)/5 (DC110V) | |
Number of auxiliary contacts: normally opened/closed | Pair | 11/11 | |||
5 | Trip switch | Rated current | A | 3(DC220V)/5 (DC110V) | |
Number of auxiliary contacts: normally opened/closed | Pair | 2/2 | |||
6 | Capacity of terminal carry continuous current | A | 10 | ||
7 | Voltage of heater and lighting circuit | V | AC220 | ||
8 | Mechanical endurance | Times | 10000 | ||
Contact Person: admin